Joint Stock Company
Mozyr Oil Refinery
From state-of-the-art technology – to top quality products

Login
FUEL OIL

Fuel Oil is used for stationary boiler plants and process units. It is produced from atmospheric and vacuum residue with the addition of HGO fractions.

Property

Unit

Test method

Specification in compliance with GOST 10585-2013

Min

Max


Kinematic viscosity at 100°C

mm2/s

STB ISO 3104

-

50.00


Ash content

%

GOST 1461

-

0.14


Mass fraction of mechanical impurities

%

GOST 6370

-

1.0


Mass fraction of water

%

GOST 2477

-

1.0


Content of water soluble acids and alkalis

-

GOST 6307, p.7.5 of GOST 10585

none


Mass fraction of sulfur

%

STB 1420

-

-

2.50

3.00


Open Cup Flash Point

°C

GOST 4333

110

-


Pour point

°C

GOST 20287 (method B)

-

25


Calorific value (lower) calculated with reference to dry fuel (net)

kJ/kg

STB 1663 (ASTM D 240)

39,900

-

   

Density at 15°C

kg/m3

GOST 31072

n/a

Determination is mandatory